1. Before each power-on operation of the dispensing machine, check that the instrument air pressure is sufficient (>0.4MPa).
2. After powering on the dispensing machine, the small circulation valve should open, unless otherwise specified; the display screen should show the data from the last dispensing. The screen next to the keypad should indicate dispensing idle time.
3. Minimize the number of large circulation pre-cooling cycles. The frequency can be determined based on defrosting progress or ambient temperature. In high ambient temperatures, the number of large circulation cycles can be increased appropriately.
4. The dispensing machine's flow meter is a mass flow meter; the solid part is not a vacuum, but filled with inert gas. Therefore, frost will form during prolonged operation. Insulating the flow meter is not recommended, as it will affect measurement accuracy.
5. Before each operation, the dispensing nozzle should be purged, especially removing ice and foreign matter from the inner sealing ring, as this can easily damage the sealing ring and shorten its lifespan.
6. The sealing gasket of the dispensing gun is easily damaged and relatively expensive. When operating, apply even pressure with both hands, first release the pressure, then tighten the handle and pull out smoothly.
7. If the inner sealing gasket of the dispensing gun is damaged, leakage will occur when the gun is pulled out. If leakage occurs during dispensing, it is generally due to damage to the outer sealing ring. The outer sealing ring is more prone to damage than the inner sealing gasket, and damage to the inner sealing gasket can easily cause injury.
8. The lifespan of the sealing rings and gaskets of the dispensing gun is calculated in cycles. Therefore, minimize the number of times the dispensing gun is inserted and removed. When not in use, the gun can be placed in the hook and not inserted into the dispensing machine's gun holder.